  • 3000 Specifications
3000 Specifications
PDF Print E-mail

Measured Parameters

Range

Resolution

Accuracy

1. AMBIENT TEMPERATURE 0-150 F 1F or C 3F
2. STACK TEMPERATURE 0-2000 F 1F or C 5F
3. OXYGEN 0-25% 0.1% 0.2%
4. SEM NITRIC OXIDE (NO)

0-1000 PPM           

1 PPM                     2% of reading*           
5. NITROGEN DIOXIDE (NO2) 0-500 PPM 1 PPM 2% of reading*
6. CARBON MONOXIDE (CO) 0-2000 PPM 1 PPM 2% of reading*
7. SEM SULFUR DIOXIDE 0-2000 PPM 1 PPM 2% of reading*
8. COMBUSTIBLES GASES 0-6% 0.01% 10% reading of CH4
9. SEM SINGLE, "DUAL RANGE" SENSOR CARBON MONOXIDE (CO) 0-2000 PPM

0-20,000 PPM

1 PPM 2% of reading*
10. SEM SINGLE, "DUAL RANGE" SENSOR NITRIC OXIDE (NO) 0-1000 PPM

0-4000 PPM

1 PPM 2% of reading*
11. TIME/DATE

Computed Parameters

Range

Resolution

Accuracy

1. COMBUSTION EFFICIENCY 0-100% 0.1%
2. CARBON DIOXIDE (CO2) 0-40% 0.1% 5% of reading
3. EXCESS AIR 0-1000% 1% 10% of reading
4. OXIDES OF NITROGEN (NOx) 0-1500 PPM 1 PPM 2% of reading*
5. EMISSIONS 1. (CO, NOx, SO2) 0-2500 milligrams/ cubic meter 2mg/m3 5% of reading*
6. EMISSIONS 2. (CO, NOx, SO2) 0.000-9.999 lbs./million BTU 0.001 lbs./ MBTU 5% of reading*
7. EMISSIONS 3. 0-9.99 grams/brake hp-hr 0.001 grams/ brake hp-hr 5% of reading*

Physical:

 1. CASE: 18" x 13" x 6" Aluminum carrying case with lock. Weight: 22 lbs. 2. PROBE: 24"L x 3/8"OD. Inconel probe with Hastelloy X sintered filter and " deflector mounted on permeation drier housing. Probe housing connects to instrument via a 10 ft. Viton(R) hose. Max. Continuous temperature: 1800 degrees F. Max sample dew point (past dryer) 50 deg F. @ 500 cc/min. (Natural gas fuel @ 0% oxygen).

Viton(R) is a registered trademark of DuPont Dow Elastomers.

Electrical Power:

 1. BATTERY: 6V rechargeable, sealed lead-acid cell. Three hour continuous battery operation. Quick 6 hour recharge.
 
2. AC: 120v.60Hz and 220V/50Hz standard.
 
3. DC: 11-40 VDC/3A standard.

Display:

0.5" High by 24 character single line LCD with backlight illumination and adjustable viewing angle.

Printer:

1. SEIKO 4", 40 char. per line thermal printer with line feed button and end of paper override.
2. TEXT MODE: 25 line printout of instant values of all measured parameters. (Time req.20 sec.)
3. PLOT MODE: Any one parameter vs. time plotted. 3 ordinate scales: full, half, quarter.
4. Time scale: selectable, 1 sec/dot-1min/dot in 1 sec/dot intervals.
5. 4 parameter plot CO-Oxygen-NOx-Efficiency, single scale
6. Calibration Certification Protocol (QA/CCP): Automatic printout of calibration test results, including sensor and filter performance status and diagnostics.
7. External Print Mode: Prints messages sent via RS-232 port.

Storage:

 1. INTERNAL: 80 individually selectable buffers hold one complete set of measurements each in non-volatile memory. Buffer contents can be set to printer or RS-232.
2. EXTERNAL: Optional pocket computer can hold 300 measurements. Near-infinite storage on a personal computer.

Communications:

 1. RS-232 PORT: RS232c port(DTE/DCE), 1200 baud default, 300-9600 baud user selectable, half duplex, N, 8, 1.
 
2. TELEPHONE PORT: Internal 1200 baud modem connects to modular phone line for remote communications.
 
3. SOFTWARE: Enercom for Windows software. 3.5" diskette, includes monitor, alarms, programming fuels, bar graphs, and multiple time plots. Also available for DOS.

Miscellaneous:

 1. FUELS: 15 fuels, 3 in foreground, 12 in background standard. Custom fuels available on request.
2. CO Alarm: selectable 0-2000 PPM in 10 PPM steps.
3. COMBUSTIBLES IN ASH: Presentable 0-100% in 5% steps.
4. MESSAGES: User friendly diagnostic and help messages.
5. CALIBRATION: Autogas span plus selectable auto zero on start.

AddThis Social Bookmark Button